RUNONRESERVE FIELD NOTES
The numbers behind your plan
These are deterministic energy estimates, calculated locally in your browser. Averaged mode spreads daily energy over 24 hours. Scheduled mode distributes daily energy through explicit operating windows in one-minute steps for up to seven days. Neither mode predicts individual compressor cycles, weather or battery electronics.
Appliance energy and average power
Daily energy (Wh) = quantity × running watts × hours per day × duty cycle
Average demand (W) = daily energy ÷ 24
Measured Wh/day is entered per unit and replaces the running-watts energy formula. Quantity multiplies once. Running and startup watts remain separate output checks. Source notes and measured status are user entries, not independent verification.
Hours are the daily operating window. Duty cycle is the fraction of that window at the stated running watts. A 100 W device in a 24-hour window at 50% duty consumes 1,200 Wh/day. Use either equivalent active hours or a duty factor to account for cycling; avoid applying the same reduction twice.
Available battery energy
Available DC Wh = nominal Wh × usable fraction × max(0, charge − reserve)
AC-only equivalent Wh = available DC Wh × inverter efficiency
Percentages are converted to fractions. Usable fraction represents capacity derating; reserve is expressed on the same charge scale as current charge. If manufacturer firmware already excludes a reserve from the quoted usable capacity, do not subtract it again. The defaults are 100% usable capacity, 100% charge, 10% reserve, 90% inverter efficiency and 8 W inverter idle.
Runtime without counting losses twice
Battery-side average W = average AC W ÷ AC efficiency + average DC W ÷ DC efficiency + idle W
Runtime (hours) = available DC Wh ÷ battery-side average W
Idle is added on the battery side throughout the modeled period if any active AC load exists. It is zero for DC-only or empty plans, assuming the inverter is off. DC efficiency defaults to 100%, so no DC conversion loss is assumed unless you enter one. Runtime with zero demand is shown as “No demand,” rather than infinite hours; zero available energy with positive demand yields zero hours.
Reference example: 2,000 Wh × 90% ÷ 100 W = 18 hours, with full usable charge, no reserve and no idle draw. At 80% efficiency this becomes 16 hours. With 80% charge, 20% reserve and 80% usable capacity, available DC energy is 960 Wh and the same 100 W load lasts 8.64 hours at 90% efficiency.
Sizing for your outage target
Required usable DC Wh = battery-side average W × target hours
Required nominal Wh = required usable DC Wh ÷ [usable fraction × max(0, charge − reserve)]
A zero available fraction makes sizing unavailable for a positive load. Capacity shortfall is the difference between required nominal energy and your entered nominal capacity. Remaining charge is an energy projection that can fall below your reserve; the runtime estimate stops at reserve. Short outages can differ greatly because the averaged baseline does not describe actual switching times. Sizing cards remain a battery-only averaged baseline; the timeline includes selected windows and charging sources.
Inverter compatibility
Continuous AC demand is the sum of running watts for all active AC appliances, without a duty reduction. Simultaneous AC startup is the sum of their startup watts. A second estimate starts only the largest incremental startup load while other appliances are running. The conservative simultaneous estimate drives warnings. Zero-hour, zero-duty and zero-watt loads are excluded.
These figures do not establish electrical compatibility. Surge duration, VA, power factor, waveform, per-outlet limits, DC current limits, transfer equipment, grounding and neutral bonding require separate review. No automatic safety margin is added.
Source data and uncertainty
Simulation, solar and generators
Scheduled windows repeat on an elapsed local clock, including midnight crossings. Inside each window, daily Wh divided by window hours is the average demand. The source model adds converted solar and AC charger energy, serves demand above reserve and caps storage at usable capacity. It records interruptions even if the battery recharges later.
Potential solar Wh/day equals array W × equivalent sun hours × generation factor. The editable flat daylight profile is an example, not a location forecast. Input limits clip generation before charging efficiency is applied; excess combined energy after the battery is full is curtailed. Cold Voc = panel Voc × series count × [1 + coefficient/100 × (minimum temperature − 25°C)], using 25°C when the entered minimum is warmer. Isc scales with parallel strings. Missing limits need verification; a documented violation excludes solar charging.
Generator fuel is linearly interpolated only between documented or entered load points. Outside that range fuel and cost are unknown; any energy projection then assumes continued fuel availability. Hybrid mode routes generator energy through a charger; direct bypass is not assumed. Unsupported or unverified charging modes are excluded. Generator-only mode does not supply DC loads through an assumed adapter.
Scenarios and costs
Conservative defaults increase demand by 20% and reduce usable nominal capacity by 10%; favorable defaults reduce demand by 20%. Efficiency stays unchanged. These are editable planning buffers, not probability or weather estimates. Optional-load previews retain medical loads and require your choice before applying.
Ten-year cost equals entered hardware, accessories and installation plus ten years of modeled annual fuel and maintenance plus one entered replacement. Annual fuel scales this outage to your entered annual usage. Prices, inflation, financing, tax credits and battery lifetime are not inferred.
Every library appliance is a generic estimate, never a manufacturer-verified specification. Some running values are chosen within the Ohio Consumers’ Counsel’s generic ranges; remaining values are authored illustrative assumptions. All hours, duty cycles and startup values are planning assumptions. The versioned dataset identifies each source and its review date. The Virginia Cooperative Extension energy guide explains watt-hours and appliance cycling.
Temperature, battery age, discharge rate, cutoff behavior, changing demand and manufacturer restrictions can reduce runtime. Measure your own equipment and retain appropriate headroom. Product snapshots are manufacturer-sourced and dated; they do not verify your installation.
Apply the numbers to your home